TROUBLESHOOTING


THIS TROUBLESHOOTING GUIDE CANNOT DESCRIBE EVERY POSSIBLE COMBINATION OF CONDITIONS RESULTING IN IMPROPER PERFORMANCE OR FAILURE OF THE GUARDIAN IGNITOR OR THE RELATED EQUIPMENT.  THE FINAL RESPONSIBILITY FOR SAFE OPERATION OF THIS DEVICE IS WITH THE OPERATOR.  NO MANUAL, NO MATTER HOW COMPLETE, CAN REPLACE SAFE OPERATING PRACTICES AND SOUND COMMON SENSE.
 
SYMPTOM PROBLEM SOLUTION
ELECTRODE FAILS TO SPARK

HEAVY SOOT    ACCUMULATION ON ELECTRODE OR PILOT TIP

REMOVE & CLEAN PILOT TIP AND ELECTRODE

IGNITION CABLE DAMAGED BROKEN OR BURNED   REPLACE WIRE
 LOW BATTERY VOLTAGE    CHARGE OR REPLACE AS REQUIRED
POOR CONNECTIONS TO ELECTRODE OR BATTERY   CLEAN & TIGHTEN ALL CONNECTIONS TO BATTERY & ON TERMINAL BLOCK
PILOT FLAME FAILS IMPROPER PLACEMENT OF ELECTRODE PLACE ELECTRODE CLOSER TO PILOT TIP TO MAXIMIZE ARC
NO SPARK ON ELECTRODE     SEE "IGNITOR FAILS TO SPARK"
NO PILOT GAS SUPPLY   CHECK FOR CLOSED VALVES OR PLUGGED ORIFICE, REGULATORS, OR STRAINER
BURNED PILOT TIP   REPLACE PILOT TIP
DOES NOT SENSE THE PILOT FLAME  ELECTRODE IMPROPERLY  PLACED  ADJUST ELECTRODE TO ASSURE GOOD FLAME CONTACT
  IMPROPER PILOT GAS PRESSURE      ADJUST PILOT FLAME TO ASSURE FLAME CONTACT WITH BOTH ELECTRODE AND PILOT TIP
  IMPROPER GROUND INSTALL GROUND WIRE FROM  PANEL TO BURNER PIPEING
  GROUND FAULT BETWEEN BATTERY NEGATIVE AND VESSEL PIPING   CHECK ALL WIRING AND VALVES FOR A SHORT TO PILOT BURNER TIP
DAMAGED IGNITION CABLE    REPLACE CABLE
GUARDIAN PANEL NOT  ELECTRICALLY GROUNDED    INSTALL GROUND WIRE FROM  PANEL TO BURNER PIPEING

 